Free humidity calculator: turn dry-bulb and wet-bulb readings into relative humidity, dew point, absolute humidity and vapour pressure deficit.
A wet-bulb and dry-bulb pair is the oldest way to measure humidity without electronics. The dry bulb reports the air temperature; the wet bulb, cooled by evaporation, reports how dry the air is. The gap between the two readings is the whole measurement.
This calculator applies the psychrometric formula recommended by the World Meteorological Organization to that gap, then reports relative humidity, dew point, absolute humidity, saturation vapour pressure and the vapour pressure deficit. It is the quick check for greenhouses, drying rooms, air handling units, weather stations and anyone calibrating a hygrometer against a sling psychrometer.
Enter both temperatures in degrees Celsius, taken at the same moment, in the shade and in moving air. The third field is the station air pressure in hPa; leave it at 1013.25 for mean sea level, or lower it by roughly 12 hPa for every 100 m of elevation so that high-altitude readings stay accurate.
The result is a spot reading rather than a forecast. Air that is warmed indoors keeps the same water content while its relative humidity falls, so compare like with like: always pair a temperature with the humidity measured at that same temperature.
Wrap the bulb in a thin cotton wick, wet it with clean water and keep air moving across it, either by slinging the thermometer or by holding it in a steady draught. Evaporation pulls heat out of the wick, so the wet bulb settles below the dry bulb and stops falling once it reaches equilibrium. Read both thermometers at the same moment, in the shade. A still, unventilated wet bulb reads too high.
The psychrometric formula subtracts A x p x (t - t_w), so pressure scales how much cooling the evaporation represents. At 800 hPa, roughly 2000 m above sea level, the same 25 °C dry and 18 °C wet pair gives 53.4 % instead of 50.3 % at 1013.25 hPa. Saturation vapour pressure depends only on temperature, so it stays the same at any pressure.
Convert them first with C = (F - 32) x 5 / 9. For instance 77 °F is 25 °C and 64.4 °F is 18 °C, which is the worked example above. Both temperatures must be entered in Celsius, because the vapour pressure constants used here are defined on the Celsius scale.